library / browse / ND-0674

ND-0674 · 2000 · Other

The effects of outdoor air supply rate in an office on perceived air quality, sick building syndrome (SBS) symptoms and productivity

Wargocki P et al. Indoor Air. 2000.

doi.org/10.1034/j.1600-0668.2000.010004222.x · Finding checked against the abstract

Source details checked refers to publication information or an official source page. See the record’s limitations for incomplete extraction and the method for how to read the labels.

What the source reports

In a real office ventilated at 3, 10 or 30 L/s per person, more outdoor air reduced dissatisfaction with the air and symptoms, and office task performance rose by about 1.7% for each doubling of ventilation.

Design questions and applications

Set ventilation above the minimum.

Field

Air and ventilation

Notes and follow-up

Added from the Corpus Desk (card wargocki-2000-ventilation) on 2026-11-09; the card finding was rewritten from the abstract. Evidence strength and translation distance not yet rated. WELL label held for review.